11-7
Address
Parameter
Scale
Unit
R/W
Allotment for Bits
0x0002
Inverter Input
Voltage
-
-
R
0 : 220V,
1 : 440V
0x0003
S/W version
-
-
R
(Ex) 0x0022 : Version 2.2
0x0004
Parameter Lock
-
-
R/W
0 : Lock(default), 1: Unlock
0x0005
Freq. Reference
0.01
Hz
R/W
Starting freq. ~ Max. freq.
0x0006
Run Command
-
-
R
B15, B14, B13 : Reserved
B12, B11, B10, B9, B8 : Freq. command
0 : DRV-00, 1 : Not Used,
2~8 : Multi-Step frequency 1~7
9 : Up, 10 : Down, 11 : Up-Down Zero
12 : V0, 13 : V1, 14 : I,
15 : V0+I, 16 : V1+I, 17 : JOG,
18 : PID, 19 : Communication,
20~31 : Reserved
B7, B6 : Run Command
0 : Terminal, 1 : Keypad, 3 : Communication
R/W
B5
Reserved
B4
Emergency stop (0->1)
B3
Fault reset (0->1)
B2
Reverse run (0->1)
B1
Forward run (0->1)
B0
Stop (0->1)
0x0007
Acceleration Time
0.1
sec
R/W
See Function List
0x0008
Deceleration Time
0.1
sec
R/W
See Function List
0x0009
Output Current
0.1
A
R
See Function List
0x000A
Output Frequency
0.01
Hz
R
See Function List
0x000B
Output Voltage
0.1
V
R
See Function List
0x000C
DC Link Voltage
0.1
V
R
See Function List
0x000D
Output Power
0.1
kW
R
See Function List
0x000E
Inverter Status
-
-
-
B0
Stop
B1
Forward running
B2
Reverse running
B3
Fault (Trip)
B4
Acceleration
B5
Deceleration
B6
Speed arrived
B7
DC Braking
B8
Stopping
B9
Not Used
B10
Brake open
B11
Forward run command
B12
Reverse run command
B13
REM. R/S
B14
REM. Freq.
B15
Reserved