[Torque boost in forward direction]
[Torque boost in reverse direction]
Set F27 to 0 {Manual torque boost}.
The values of [Torque boost in forward/reverse direction] are set separately in F28 and
F29.
If the boost value is set much higher than required, it may cause motor overheating due to
over-energizing.
Before Auto Torque Boost setting, H34 and H42 should be set correctly (See page 10-6,
10-10).
Select 1{Auto torque boost} in F27.
Inverter automatically calculates torque boost value using motor parameters and outputs
the corresponding voltage.
FX
Time
RX
Voltage
FX torque
boost
No torque boost
100%
RX torque
boost
For Service Call 800-848-2504