7-19
Manual torque boost
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Function
group 1
F27
[Torque Boost select]
0
0 ~ 1
0
F28
[Torque boost in forward direction]
-
0 ~ 15
2
%
F29
[Torque boost in reverse direction]
Set F27 to 0 {Manual torque boost}.
The values of [Torque boost in forward/reverse direction] are set separately in F28 and
F29.
CAUTION
If the boost value is set much higher than required, it may cause motor overheating due to
over-energizing.
Auto torque boost
Group
Code
Parameter Name
Setting
Range
Initial
Unit
Function group 1
F27
[Torque Boost select]
1
0 ~ 1
0
Function group 2
H34
[No load motor
Current]
-
0.1 ~ 100
-
A
H41
[Auto tuning]
0
0 ~ 1
0
H42
[Stator resistance (Rs)]
-
0 ~ 28
-
Before Auto Torque Boost setting, H34 and H42 should be set correctly (See page 10-6,
10-10).
Select 1{Auto torque boost} in F27.
Inverter automatically calculates torque boost value using motor parameters and outputs
the corresponding voltage.
FX
Time
RX
Voltage
FX torque
boost
No torque boost
100%
RX torque
boost
For Service Call 800-848-2504
For Service Call 800-848-2504

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS sv-ig5a and is the answer not in the manual?

LSIS sv-ig5a Specifications

General IconGeneral
BrandLSIS
Modelsv-ig5a
CategoryInverter
LanguageEnglish

Related product manuals