Chapter 5 Thermocouple Input Module (XBF-TC04S,TC04B) 
 
 
(6) Average value setting area (Address 14~17) 
(a) Average value can be set per channel. 
(b) In case average processing method is sampling, values of this area are ignored. 
(c) In case of using PUT instruction, average value setting address is as follows. 
 
B15  B14  B13  B12  B11  B10  B9  B8  B7  B6  B5  B4  B3  B2  B1  B0 
CH# average value setting 
Time-average: 400 ~ 64000[ms] 
Count-average: 2 ~ 64000[times] 
Moving-average: 2 ~ 100   
 
(d) When input is out of range, the min. value of each address is selected by force. 
But, U0x.01.8~ U0x.01.B  (setting error representation, in case of IEC type, %UX0.x.24 
~ %UX0.x.27) are on, error information is displayed at bit 3~5 of address 27~30. 
(Bit 3: time-average, bit 4: count-average, bit 5: moving-average) 
Ex.) When selecting the Time-average and setting average value as 200, 400ms is selected in 
address “14” by force. 
(e) This area shows the same results with average value setting in I/O parameter setting window. 
In the I/O parameter setting window, prohibition function is provided not to set value that is out 
of range. (In case of setting value that is out of range, that values are displayed with red color 
and error message is displayed.)  
1) Time-Avr. 
 
2) Count-Avr. 
 
3) Moving-Avr. 
 