XGB Analog edition manual
14.4 Conversion Characteristic of each Output Range
The output conversion characteristic is described by graphs as follows after changing digital input set from
XBG basic unit to analog output (Voltage, Current).
In the digital input range, there are four kinds of value. Those are unsigned value, signed value, precise
value, percentile value.
I/O conversion characteristic is as follows depending on each range of digital input.
1) Conversion characteristic of analog output module (XBF-DV04C)
Analog
output
value
-10V
-5V
0V
5V
10V
10.24
-10.24
0V
1.25V
2.5V
3.75V
5V
5.06
-0.06
1V
2V
3V
4V
5V
5.048
0.952
Percentile value
Unsigned value
5000
0 8000 16000
Digital
input value
P
r
a
c
t
i
c
a
l
r
a
n
g
e
o
Offset value
Gain value
Signed value
-8000
0
8000
10000
0
16191
8191
10119
-191
-8192
-120
0V
2.5V
5V
7.5V
10V
10.12
-0.12
(1) DC 1 ~ 5V Output range
Digital input
Analog output voltage (V)
Unsigned value
(-192 ~ 16,191)
-192 0 4,000 8,000 12,000 16,000 16,191
Signed value
(-8,192 ~ 8,191)
-8,192 -8,000 -4,000 0 4,000 8,000 8,191
Precise value
(952 ~ 5,047)
952 1,000 2,000 3,000 4,000 5,000 5,047
Percentile value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
(2) DC 0 ~ 5V Output range
Digital value
Analog output voltage (V)
Unsigned value
(-192 ~ 16,191)
-192 0 4,000 8,000 1,2000 16,000 16,191
Signed value
(-8,192 ~ 8,191)
-8,192 -8,000 -4,000 0 4,000 8,000 8,191
Precise value
(-60 ~ 5,059)
-60 0 1,250 2,500 3,750 5,000 5,059
Percentile value
(-120 ~ 10,119)
-120 0 2,500 5,000 7,500 10,000 10,119
14 - 6