Chapter 15 PID Function (Built-in function) 
 
15 - 51 
 
 
 - In the example, auto-tuning using PWM is not executed. Therefore, PWM output is set 
as disabled. 
 
 
 SV: 1000(2.5V) 
- It shows an example in which XBF-AD04A is set as the voltage input of 0~10V 
 
 Operation cycle: 1000 
- In the example, it is set that PID control is executed every 100ms.   
 
 Proportional gain, integral time and differential time 
    -  It  should be  initially set  as  1,0,0 because  PID  auto-tuning  results is  used  with PID 
constant.   
 
 Max. MV: 4000 
 - Max. MV is set as 4000. If MV is 4000, XBF-DV04A outputs 10V. 
 
 DeadBand: 0 
 - It is set as 0 because the example does not use DeadBand function. 
 
 Differential filter setting: 0 
 - it is also set as 0 because the example does not use differential filter. 
 
 Min. MV: 0 
- Min. MV is set as 0. If MV is 0, XBF-DV04A outputs 0V. 
 
 PWM junction, PWM output cycle 
- It is not necessary to set them because the example does not use PWM output. 
 
 SV ramp, PV follow-up: 0 
- It is not necessary to set SV ramp and PV follow-up because the example does not 
use them.   
 
 Min. PV, Max. PV: 0 
-  Set  them  as  0  and  4000  respectively  so  that  it  could  be  identical  with  A/D  input 
module’s input scope.