EasyManua.ls Logo

Lucent 5ESS DRM - Page 322

Default Icon
642 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.11.5.1 Verify Timing Reference Connections for MCTSI Side 1
1. With MCTSI-0 active, remove MCTSI-1 from service: type and enter: 201 (1190,a
CMD)
Response: RMV MCTSI = a–1 COMPLETED
Where: a = Switching module number.
2. At the MCTSI cabinet, side 1, Power and Control Display (PCD) pack, depress:
OFF button.
Response: REPT PWR OFF MCTSI = a–1
Where: a = Switching module number.
3. Visually verify connection of output clock reference cable as shown below.
FROM TO
BITS BOX
(see Figure 5.11-2)
TSICOM-1
(see Figure 5.11-3)
EQL 62-116 (TSIU4), 353 (Berg Connector)
EQL 53-017 (TSIU4-2), 353 (Berg
Connector)
BITS BOX TELECOM SOLUTIONS®
DCD-523
S
S
T
T
R
R
W/BL
BL/W
O/W
W/O
OUTPUT MODULE (N)
(WIREWRAP VERSION)
OUTPUT MODULE (N+1)
(WIREWRAP VERSION)
Figure 5.11-2
Telecom Solutions
BITS BOX Cabling Connection
ROUTINE MAINTENANCE
Procedure 5.11
235-200-150
January 2003
Page 5.11-4 Issue 3.00

Table of Contents