MI 3152(H) EurotestXC (2,5 kV) Technical specifications
177
12.2 Diagnostic test (MI 3152H only)
Uiso: 500V, 1000 V, 2500 V
DAR – Dielectric absorption ratio
(5 % of reading + 2 digits)
PI
– Polarization index
(5 % of reading + 2 digits)
For Riso, R60, and Um sub-results technical specifications defined in chapter 12.1 R iso –
Insulation resistance apply.
12.3 R low – Resistance of earth connection and
equipotential bonding
Measuring range according to EN 61557 is 0.16 ... 1999 .
R – Resistance
(3 % of reading + 3 digits)
R+, R – Resistance
(5 % of reading + 5 digits)
Open-circuit voltage ................................ 6.5 VDC ... 18 VDC
Measuring current ................................... min. 200 mA into load resistance of 2
Test lead compensation .......................... up to 5
The number of possible tests .................. > 1400, with a fully charged battery
Automatic polarity reversal of the test voltage.
12.4 Continuity – Continuous resistance measurement with
low current
R – Continuity resistance
(5 % of reading + 10 digits)
Open-circuit voltage ................................ 6.5 VDC ... 18 VDC
Short-circuit current ................................ max. 8.5 mA