7.3 The DAR and PI diagnostic (MI 3152H only)
DAR (Dielectric Absorption Ration) is ratio of insulation resistance values measured after 15
seconds and after 1 minute. The DC test voltage is present during the whole period of the
measurement.


󰇛

󰇜

󰇛

󰇜
PI (Polarization Index) is the ratio of insulation resistance values measured after 1 minute and
after 10 minutes. The DC test voltage is present during the whole period of the measurement


󰇛

󰇜

󰇛

󰇜
For additional information regarding PI and DAR diagnostic, please refer to Metrel’s handbook
Modern insulation testing.
Figure 7.10: Diagnostic test menu
Measurement parameters / limits
Uiso
Nominal test voltage [500 V, 1000 V, 2500 V]
Connection diagrams
Figure 7.11: Connection of 3-wire test lead and Tip commander (U
N
1 kV)