MI 3152(H) EurotestXC (2,5 kV) Technical specifications
178
Test lead compensation .......................... up to 5
12.5 RCD testing
General data
Nominal residual current (A,AC) ............. 10 mA, 30 mA, 100 mA, 300 mA, 500 mA,
1000 mA
Nominal residual current accuracy .......... -0 / +0.1I; I = IN, 2IN, 5IN
-0.1I / +0; I = 0.5IN
AS/NZS 3017 selected: ± 5 %
Test current shape .................................. Sine-wave (AC), pulsed (A, F), smooth DC (B, B+)
DC offset for pulsed test current ............. 6 mA (typical)
RCD type ................................................ (non-delayed), S (time-delayed), PRCD, PRCD-K,
PRCD-S
Test current starting polarity .................. 0º or 180º
Voltage range ......................................... 93 V ... 134 V (45 Hz ... 65 Hz)
185 V ... 266 V (45 Hz ... 65 Hz)
RCD test current in relation to RCD type, nominal RCD current and multiplication factor
I
N
× 1/2
(mA)
I
N
× 1
(mA)
I
N
× 2
(mA)
I
N
× 5
(mA)
RCD I
I
N
(mA)
AC
A, F
B, B+
AC
A, F
B, B+
AC
A, F
B, B+
AC
A, F
B, B+
AC
A, F
B, B+
10
5
3.5
5
10
20
20
20
40
40
50
100
100
30
15
10.5
15
30
42
60
60
84
120
150
212
300
100
50
35
50
100
141
200
200
282
400
500
707
1000
300
150
105
150
300
424
600
600
848
×
1500
×
×
500
250
175
250
500
707
1000
1000
1410
×
2500
×
×
1000
500
350
500
1000
1410
×
2000
×
×
n.a.
×
×
×
× ............................................................. not applicable
............................................................. applicable
AC type................................................... sine wave test current
A, F types…… ........................................ pulsed current
B, B+ types ............................................. smooth DC current (MI 3152 only)
RCD test current in relation to MI / EV RCD type and multiplication factor
I
N
× 1/2
(mA)
I
N
× 1
(mA)
I
N
× 2
(mA)
I
N
× 5
(mA)
RCD I
I
N
(mA)
MI / EV a.c.
MI / EV a.c.
MI / EV a.c.
MI / EV a.c.
MI / EV a.c.
MI / EV d.c.
30 a.c.
15
30
60
150
×
6 d.c.
×
×
×
×
×
×. ............................................................ not applicable
. ............................................................ applicable
MI / EV types (a.c. part) .......................... sine-wave test current
MI / EV types (d.c. part) .......................... smooth DC current
12.5.1 RCD Uc Contact voltage
Measuring range according to EN 61557 is 20.0 V ... 31.0 V for limit contact voltage 25 V
Measuring range according to EN 61557 is 20.0 V ... 62.0 V for limit contact voltage 50 V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL EurotestXC MI 3152 and is the answer not in the manual?

METREL EurotestXC MI 3152 Specifications

General IconGeneral
BrandMETREL
ModelEurotestXC MI 3152
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals