MI 3152(H) EurotestXC (2,5 kV) Technical specifications
181
12.8 Zs rcd – Fault loop impedance and prospective fault
current in system with RCD
Z – Fault loop impedance
Measuring range according to EN 61557 is 0.46 ... 9.99 k for I test = standard and 0.48 ...
9.99 k for I test = low.
Accuracy
I test = standard
(5 % of reading + 10
digits)
(5 % of reading + 12
digits)
Accuracy may be impaired in case of heavy noise on mains voltage.
Ipsc – Prospective fault current
Consider accuracy of fault
loop resistance measurement
Ulpe – Voltage
(2 % of reading + 2 digits)
Uc – Contact voltage
Refer to chapter 12.5.1 RCD Uc – Contact voltage for detailed technical specification.
Nominal voltage range ........................... 93 V ... 134 V (45 Hz ... 65 Hz)
185 V ... 266 V (45 Hz ... 65 Hz)
No trip out of RCD. R, X
L
values are indicative.
12.9 Z loop m – High precision fault loop impedance and
prospective fault current
Refer to A 1143 – Euro Z 290 A adapter Instruction manual for detailed technical
specification.