58
Configuration
Command Menu - FA-300 Config - Features
13 Signal Isolators
[ ] ENABLE
[X] DISABLE ->Def
Isolators on signal
circuits
Enable this function only when
suite isolators are used
(Canada only).
Command Menu - FA-300 Config - Features
14 Strobe Type
[X] NORMAL ->Default
[ ] MIRCOM
[ ] FARADY
[ ] WHEELOCK
[ ] GENTEX
[ ] SYSTEM SENSOR
Strobe
Use this menu to select the
manufacturer of the strobes
used in the system. The
selection is system-wide and
applies to all indicating circuits
configured as strobes. For
NORMAL strobes there is no
synchronization, while other
strobes use the manufacturer’s
protocol to synchronize the
strobes.
Command Menu - FA-300 Config - Features
15 Signal rate (Evacuation code)
[X] TEMPORAL->Def
[ ] CONTINOUS
[ ] MARCH TIME
[ ] CALIFORNIA
Signal rate
Use this function to set the rate
at which the indicating circuits
sound.
Command Menu - FA-300 Config - Features
16 Active EOL
[X] DISABLE->Default
[ ] ENABLE
Active end-of-line
Enable this function if you are
using an active end-of-line
resistor. Enable this function if
you are using the ICAC-306
(the ICAC-306 has built in
active end-of-line resistors).
Table 7 Feature Config menu
Feature Default
Name in the
FA-300
Configuration Utility
Description
Sig-Sil. Isolator
[X] DISABLE