174
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
6 Output Specification and External Wiring
6.2 Transistor Output
6. Output current
The ON voltage of the output transistor is approx. 1.5V.
When driving a semiconductor element, carefully check the input voltage characteristics of the applied
element.
*1. When using an instruction related to pulse train output or positioning, make sure to set the load
current to 10 to 100mA (5 to 24V DC).
7. Open circuit leakage current
0.1mA or less
Model Output current Limitation
Main units
Y000 to Y003 0.3A/1 points
*1
Make sure that the total load current of resistance loads per
common terminal (16points/common) is 1.6A so that
temperature rise is restrained.
Y004 or later 0.1A/1 points
Extension
blocks
FX
2NC-16EYT(-DSS)
FX
2NC-32EYT(-DSS)
0.1A/1 points
Make sure that the total load current of 8 resistance load
points is 0.8A or less.
FX
2N-16EYT-C 0.3A/1 points
Make sure that the total load current of 16 resistance load
points is 1.6A or less.
FX
2N-8EYT(-ESS/UL)
FX
0N-8EYT
FX
2N-16EYT(-ESS/UL)
FX
0N-16EYT
0.5A/1 points
The total load current of resistance loads per common
terminal should be the following value.
4points/common: 0.8A
8points/common: 1.6A
FX
2N-8EYT-H
FX
0N-8EYT-H
1A/1 points
Make sure that the total load current of 4 resistance load
points is 2A or less.

Table of Contents

Other manuals for Mitsubishi FX3UC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3UC Series and is the answer not in the manual?

Mitsubishi FX3UC Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3UC Series
CategoryController
LanguageEnglish

Related product manuals