298
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.13 Editing the detailed remote station information
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
4 Specifying a reserved station (Reserved station flag (b = 15): ON)
(Setting in GX Developer)
Input a reserved station specification to [Setting value] on the device test window, and click [Set].
(In "Example 2", set [Setting value] to "8904", [Hex] and [16 bit integer], and click [Set].
When specifying a reserved station, set the reserved station flag (b15) to ON.
When the reserved station flag is set to ON, the system does not detect wire breakage or other errors for
the non-connected remote station.
When the reserved station flag is set to OFF, the system detects wire breakage and/or other errors for the
non-connected remote station.
5 Writing data to the EEPROM
(Setting in GX Developer)
After setting detailed remote station information, specify writing to the EEPROM [BFM #27 (1Bh)
b4 OFF ON].
Set the buffer memory address to #27 [Dec] in the device test window. Set the [Setting value] to
"0010", [Hex] and [16 bit integer], and click [Set].
6 Confirming completion of writing to the EEPROM
(Setting in GX Developer)
Check whether BFM #28 (1Ch) b4 is ON in the buffer memory batch monitor.
When BFM #28 b4 is ON, writing to the EEPROM is completed.
For details on EEPROM write completion, refer to Subsection 9.18.10.
7 Setting the DIP switches for the operation setting to "ONLINE mode" in the
built-in master
(Setting in the PLC)
Set the built-in master to ONLINE mode (DIP switch 6: OFF), and turn ON the power again.
8 Confirming that the specified reserved station is correct
(Setting in GX Developer)
Check in the buffer memory batch monitor whether the detailed remote station information [BFM
#32 (20h) to BFM #95 (5Fh)] agrees with the changed contents.

Table of Contents

Other manuals for Mitsubishi FX3UC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3UC Series and is the answer not in the manual?

Mitsubishi FX3UC Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3UC Series
CategoryController
LanguageEnglish

Related product manuals