7 - 6
7.1 Power Supply Wiring
7.1.5 The cause of malfunctions related wiring/Remedy
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
PART NAME
5
EMC DIRECTIVE
6
INSTALLATION
7
WIRING
8
OPTION
Remedy 1 (Refer to the figures Remedy 1-1 and 1-2 below.)
If the electric potential difference between the ground cable and the panel that houses the GOT is creating
problems, connect the ground cable to the panel also.
If the wiring method as shown in Remedy 1-1 is not feasible, follow Remedy 1-2.
If taking Remedy 1 worsens noise interference, taking Remedy 2 may alleviate it.
Remedy 2 (Refer to the figures Remedy 2-1 and 2-2 below.)
Attach a ferrite core to the cable if noise from the GOT panel has adverse effects on the GOT when
Remedy 1 is taken.
Wind the wire around the ferrite core several times (approx. 3 times), if a ferrite core is used.
If the wiring method as shown in Remedy 2-1 is not feasible, follow Remedy 2-2.
FG
Ground cable from
the panel that houses
control equipment
Connection cable
Panel
grounding
Remedy1-1
Use the thickest
cable possible.
Ground cable from
the panel that houses
control equipment
Connection cable
Panel
grounding
Remedy1-2
Use the thickest
cable possible.
MITSUBISHI
GOT
1000
MITSUBISHI
GOT
1000
FG
Ground cable from
the panel that houses
control equipment
Connection cable
Remedy2-1
Use the thickest
cable possible.
FG
Ground cable from
the panel that houses
control equipment
Connection cable
Panel
grounding
Remedy2-2
Use the thickest
cable possible.
FG
Ferrite core
MITSUBISHI
GOT
1000
MITSUBISHI
GOT
1000
Panel
grounding
Ferrite core