11 - 2
11.1  Standard I/F Setting
11.1.3  Display contents of standard I/F
11.1.3 Display contents of standard I/F
Described below are the display items on the standard I/F setting menu and their functions.
1 Display item column
(1) Communication interface selection button
Select the communication interface to be displayed.
The standard interface includes the following two types.
   Standard I/F-1: For communication with PLC and microcomputer
   Standard I/F-2: For communication with PC (GT Designer2), transparent
(2) Standard interface display BOX
Displays communication interface.
Whether an RS-422 or an RS-232 interface (Standard I/F-1) for communication with PLC is used 
depends on the GOT model.
• GT1020-LBD/LBL: RS-422 fixed
• GT1020-LBD2 : RS-232 fixed
The type of the interface (Standard I/F-2) for connection to PC is always RS-232.
Standard interface display BOX
Driver display BOX
Communication interface selection button
Channel no. display BOX
Touch  Standard I/F-1 .
Touch  Standard I/F-2 .
RS-232
(FG)
INPUT
24VDC
+
-
RS-422
CSB
SDA
SDB
RDA
RDB
SG
RSA
RSB
CSA
Standard I/F-2Standard I/F-1