How To Set The Softstart Control Rate Cha
ter Six: Remote O
eration
84
How To Check the Softstart Rate
Issue the RS-232 request:
R
xx
ENTER
where
xx
= 15 for set point A
16 for set point B
17 for set point C
18 for set point D
19 for set point E
20 for the analog set point
21 for valve open
22 for valve close
The 651 controller responds with the message:
I
x
value
where
x
= 1 for set point A
2 for set point B
3 for set point C
4 for set point D
5 for set point E
6 for the analog set point
7 for valve open
8 for valve close
value
= softstart rate, expressed as a percent of full speed
(between 0.1 and 100%)