MSENSE
®
DGA 9 7045899/02 EN – 11.2020 Page 124
Modbus
function
code
Modbus
address
Dec. / Hex
Register
Address
1)
(5 digit dec.)
MSENSE
®
DGA 9
0x04
Read
Input
Register
4000 / FA0
...
4001 / FA1
4002 / FA2
...
4003 / FA3
34001
...
34002
34003
...
34004
Query ageing rate
Operating time reduction [s]
Operating time [s]
The values are transferred in each case to two
MODBUS register addresses as an unsigned, 32-
bit integer value.
0x04
Read
Input
Register
5000 / 1388
…
5001 / 1389
5002 / 138A
…
5003 / 138B
35001
…
35002
35003
…
35004
Query system status register
System fault
Extraction unit
The value is transmitted in 2 MB registers as 32-bit
unsigned number in big endian format. The value
0 indicates the fault-free function of the device.
0x06
Write
Single
Register
0 / 0
...
1 / 1
40001
...
40002
Holding register
Test register #1, #2
There are 2 freely configurable registers available
to test the write functions. (The reset initialisation
values of the two registers are 0xA5A5 and
0x5A5A.)
0x06
Write
Single
Register
1000 / 3E8
41001
Alarm acknowledgement
Alarm status #16 .. #1
The alarm acknowledgements are summarised in
a register as a coded alarm field. (Alarm #16 ->
0x8000, Alarm #1 -> 0x0001).
If a zero is written in the corresponding position
the active alarm is acknowledged. If the register is
written '0000' all the alarms are acknowledged.
0x06
Write
Single
Register
2000 / 7D0
42001
Switching off MODBUS
Switching off MODBUS
It is possible to switch off the MODBUS protocol
via MODBUS. This is done by writing 0x00FF into
the register.