DGA 9 7045899/02 EN – 11.2020 Page 75
6.2.6 Filling level L2
In this process step, the extraction chamber is filled with oil up to filling level L2 and the gaseous air is
forced from the extraction chamber into the measurement cell.
Filling level L0 “reached”
Filling level L1 “reached”
Filling level L2 “reached”
Flow F1 “present - filling”
Valve V1 “filling - draining”
Compressor K1 "standstill”
Safety functions and fault detection Filling level L2
Filling sensors zero acknowledgement, low and high
Filling level L0, L1 or L2 reached
Filling sensors zero acknowledgement, low and high
Flow measurement
Time monitoring
• Flow stops
• Drain the flow
• Filling level timeout (prevents the
flooding of the measurement cell)