DGA 9 7045899/02 EN 11.2020 Page 16
Never operate the MSENSE
®
DGA 9 on a close transformer valve for longer
periods. Please remove the device if this can not be prevented. Always
heed the removal instructions.
Never install the MSENSE
®
DGA 9 on a knee pipe or pipe bend on the in-
take side of the cooling system pump!!
Turbulence in pipe bends can result in a vacuum that can cause problems on
the device.
Never mount the MSENSE® DGA 9 on galvanised connections or valves.
Never use a high-pressure cleaner to clean the MSENSE® DGA 9.
Galvanised connections or valves can react with the oil, which can lead to er-
roneous readings.
High-pressure cleaners that are used to clean the transformer can cause
serious damage to the MSENSE® DGA 9.
High pressure cleaners used to clean the transformer could cause serious dam-
age to the MSENSE® DGA 9.
Never use multiple slip-joint pliers.
The use of such tools can damage the surfaces of the connection unit and
those of the connecting thread. Use an M55 open-ended spanner or a 1½" ad-
justable spanner.
Note!!!
Incorrect or improper handling of the connection unit, such as vacuum,
paint or solvent, will lead to expiry of the warranty claim.
The device may only be mounted and operated in restricted working ar-
eas which are not freely accessible!