Section 75 00-02-0878
2013-03-07 - 88 -
RMI Water
This RMI input is used for measuring the cooling water temperature.
Temperature
RMI Sensor Type
Type 1 Type 2 Type 3 Type 4
°C °F Ω Ω Ω Ω
40 104 291.5 480.7 69.3
50 122 197.3 323.6
60 140 134.0 222.5 36.0
70 158 97.1 157.1
80 176 70.1 113.2 19.8
90 194 51.2 83.2
100 212 38.5 62.4 11.7
110 230 29.1 47.6
120 248 22.4 36.8 7.4
130 266 28.9
140 284 22.8
150 302 18.2
NOTE: The configurable type is configurable with eight points in
the range 0-480 Ω. The temperature as well as the resistance can
be adjusted.
NOTE: If the RMI input is used as a level switch, then be aware
that no voltage must be connected to the input. If any voltage is
applied to the RMI inputs, it will be damaged. Please refer to the
Application Notes for further wiring information.