EasyManua.ls Logo

Nidec Unidrive M600 Series - Page 114

Nidec Unidrive M600 Series
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety
information
Introduction
Product
Information
System
design
Mechanical
Installation
Electrical
Installation
Getting
started
Optimization Parameters
Technical
data
Component
sizing
Diagnostics
UL
Information
114 Unidrive M Regen Design Guide
Issue Number: 4
Figure 6-9 Unidrive M rectifier power connections
* See section 6.1.2 Ground connections on page 115.
UVW
+DC BR
AC supply connections
*
Regen drive
Vac supply
UVW
+DC BR
Motor connections
*
Motoring drive
L1 L2 L3
Supply
Rectifier
ground
+DC -DC
Internal
EMC filter
*
PE
+DC
PE
-DC
PE
*
Must be
removed
+DC -DC
Internal
EMC filter
*
PE
Used as softstart
only
Motor
Optional ground
connection
DC connections
(High current DC
to motoring drive/s)
9D
10D
9D
10D
10
CAUTION
The internal EMC filter must be removed
from all drives in the regen system
(motoring and regen).
Must be
removed
The user must provide a means of preventing live parts from being touched. A cover around the electrical connections at the top of
the inverter and the bottom of the rectifier where the cables enter is required.
WARNING

Table of Contents

Related product manuals