120 Unidrive M Regen Design Guide
Issue Number: 4
Table 6-5 AC Input current and fuse ratings (690 V)
* These fuses are fast acting.
Table 6-6 Unidrive M Rectifier AC Input current and fuse ratings
* Twin rectifier
Ensure cables used suit local wiring regulations.
Model
Typical input
current
Maximum
continuous
input current
Maximum
overload input
current
Fuse rating
IEC UL / USA
Nominal Maximum
Class
Nominal Maximum
Class
AA AAA AA
07600190
18
20 32 25
50
gG
25
50
CC, J
or T*
07600240
23
26 41 32 30
07600290
28
31 49 40 35
07600380
36
39 65
50 50
07600440
40
44 75
80 80
07600540
57
62 92 80 80
08600630
74
83 121 125 125
gR
100 100
HSJ
08600860
92
104 165 160 160 150 150
09601040
124
149 194 150 150
gR
150 150
HSJ
09601310
145
171 226 200 200 200 200
10601500
180
202 268 225 225 gR 250 250
HSJ
10601780
202
225 313 250 250 gR 250 250
11602100
225
256 379
400 400 gR 400 400 HSJ11602380
271
302 425
11602630
298
329 465
Model
Typical input
current
Maximum
continuous
input current
Maximum
overload input
current
Fuse rating
IEC UL/USA
Nominal Maximum
Class
Nominal Maximum
Class
AA A
AA AA
10204100 333 361 494 450 450
gR
450 450
HSJ
10404520 370 396 523 450 450 450 450
10502430 202 218 313 250 250 250 250
10602480 202 225 313 250 250 250 250
11406840 557 594 752 630 630
gR
600 600
HSJ
11503840 313 338 473 400 400 400 400
11604060 331 362 465 400 400 400 400
1142X400* 2 x 326 2 x 358 2 x 516 400 400 400 400
1162X380* 2 x 308 2 x 339 2 x 488 400 400 400 400
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.