122 Unidrive M Regen Design Guide
Issue Number: 4
Table 6-9 AC cable ratings (575 V)
Table 6-10 AC cable ratings (690 V)
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input Output Input Output
Nominal Max
Install
method
Nominal Max
Install
method
Nominal Max Nominal Max
06500150
4
25 B2
4
25 B2
10
3
10
3
06500190
6
61010
06500230
10
10
88
06500290 66
06500350
16
66
07500440
16
25 B2
16
25 B2
4
3
4
3
07500550
25 25
33
08500630
35
50 B2
35
50 B2 1 1 1 1
08500860
50 50
09501040
2 x 70
2 x 185
B2
2 x 35 2 x 150
B2
2 x 1 2 x 500 2 x 3 2 x 350
09501310
2 x 70
2 x 185 2 x 50 2 x 150 2 x 1 2 x 500 2 x 1 2 x 350
10501520
2 x 70
2 x 185
B2
2 x 70 2 x 150
B2
2 x 2/0 2 x 500 2 x 2/0 2 x 350
10501900
2 x 95
2 x 185 2 x 70 2 x 150 2 x 2/0 2 x 500 2 x 2/0 2 x 350
11502000
2 x 70
C
2 x 70
C
2 x 3/0 2 x 3/0
11502540
2 x 95
2 x 95 2 x 4/0 2 x 4/0
11502850
2 x 120
2 x 120 2 x 250 2 x 250
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG or Kcmil
Input Output Input Output
Nominal Max
Install
method
Nominal Max
Install
method
Nominal Max Nominal Max
07600190
10
25 B2
10
25 B2
8
3
8
3
07600240 66
07600290 66
07600380
16 16
44
07600440
16 16
44
07600540
25 25
33
08600630
50
70 B2
50
70 B2
2
1/0
2
1/0
08600860
70 70
1/0 1/0
09601040
2 x 50
2 x 185
B2
2 x 35 2 x 150
B2
2 x 1 2 x 500 2 x 3 2 x 350
09601310
2 x 70
2 x 185 2 x 50 2 x 150 2 x 1/0 2 x 500 2 x 1 2 x 350
10601500
2 x 70
2 x 185
B2
2 x 70 2 x 150
B2
2 x 2/0 2 x 500 2 x 1/0 2 x 350
10601780
2 x 95
2 x 185 2 x 70 2 x 150 2 x 3/0 2 x 500 2 x 2/0 2 x 350
11602100
2 x 70
C
2 x70
C
2 x 3/0 2 x 3/0
11602380
2 x 95
2 x 95 2 x 4/0 2 x 4/0
11602630
2 x 95
2 x 95 2 x 250 2 x 250