Safety
information
Introduction
Product
Information
System
design
Mechanical
Installation
Electrical
Installation
Getting
started
Optimization Parameters
Technical
data
Component
sizing
Diagnostics
UL
Information
Unidrive M Regen Design Guide 151
Issue Number: 4
Table 9-3 Voltage ratings dependant values
VM_USER_CURRENT_HIGH_RES
Range applied to torque reference and percentage load parameters with two decimal
places
Units %
Range of [MIN] -1000.00 to 0.00
Range of [MAX] 0.00 to 1000.00
Definition
VM_USER_CURRENT_HIGH_RES[MAX] = User Current Maximum Scaling (04.024) with an additional decimal place
VM_USER_CURRENT_HIGH_RES[MIN] = -VM_USER_CURRENT_HIGH_RES[MAX]
User Current Maximum Scaling (04.024) defines the variable maximum/minimums VM_USER_CURRENT and
VM_USER_CURRENT_HIGH_RES which are applied to Percentage Load (04.020), Torque Reference (04.008) and
Torque Offset (04.009). This is useful when routing these parameters to an analog output as it allows the full scale
output value to be defined by the user. This maximum is subject to a limit of MOTOR1_CURRENT_LIMIT or
MOTOR2_CURRENT_LIMIT depending on which motor map is currently active.
The maximum value (VM_TORQUE_CURRENT_UNIPOLAR [MAX] varies between drive sizes with default
parameters loaded. For some drive sizes the default value may be reduced below the value given by the parameter
range limiting.
Variable min/max
Voltage level (V)
200 V 400 V 575 V 690 V
VM_DC_VOLTAGE_SET[MAX] 400 800 955 1150
VM_DC_VOLTAGE[MAX] 415 830 990 1190
VM_AC_VOLTAGE_SET[MAX] 265 530 635 765
VM_AC_VOLTAGE[MAX] 325 650 780 930
VM_STD_UNDER_VOLTS[MIN] 175 330 435 435
VM_SUPPLY_LOSS_LEVEL[MIN] 205 410 540 540
VM_HIGH_DC_VOLTAGE 1500 1500 1500 1500