174 Unidrive M Regen Design Guide
Issue Number: 4
Table 9-8 Menu 6 Regen parameter descriptions
Parameter Range() Default()Type
06.010 Enable Conditions 000000000000 to 111111111111 RO Bin ND NC PT
06.011 Sequencer State Machine Inputs 000000 to 111111
RO Bin ND NC PT
06.015 Drive Enable Off (0) or On (1) On (1) RW Bit US
06.016 Date 00-00-00 to 31-12-99 00-00-00 RW Date ND NC PT
06.017 Time 00:00:00 to 23:59:59 00:00:00 RW Time ND NC PT
06.018 Day Of Week
Sunday (0), Monday (1), Tuesday (2), Wednesday (3),
Thursday (4), Friday (5), Saturday (6)
RO Txt ND NC PT
06.019 Date/Time Selector
Set (0), Powered (1), Running (2), Acc Powered (3),
Local Keypad (4), Remote Keypad (5), Slot 1 (6),
Slot 2 (7), Slot 3 (8), Slot 4 (9)
Powered (1) RW Txt US
06.020 Date Format Std (0) or US (1) Std (0) RW Txt US
06.021 Time Between Filter Changes 0 to 30000 Hours 0 Hours RW Num US
06.022 Filter Change Required / Change Done Off (0) or On (1) Off (0) RW Bit ND NC
06.023 Time Before Filter Change Due 0 to 30000 Hours
RO Num ND NC PT PS
06.024 Reset Energy Meter Off (0) or On (1) Off (0) RW Bit
06.025 Energy Meter: MWh ±999.9 MWh
RO Num ND NC PT PS
06.026 Energy Meter: kWh ±99.99 kWh
RO Num ND NC PT PS
06.027 Energy Cost Per kWh 0.0 to 600.0 0.0 RW Num US
06.028 Running Cost ±32000
RO Num ND NC PT
06.029 Hardware Enable Off (0) or On (1)
RO Bit ND NC PT
06.041 Drive Event Flags 00 to 11 00 RW Bin NC
06.042 Control Word 000000000000000 to 111111111111111 000000000000000 RW Bin NC
06.043 Control Word Enable Off (0) or On (1) Off (0) RW Bit US
06.044 Active Supply Off (0) or On (1)
RO Bit ND NC PT
06.045 Cooling Fan control -10 to 11 10 RW Num US
06.046 Cooling Fan Speed 0 to 10
RO Num ND NC PT
06.060 Standby Mode Enable Off (0) or On (1) Off (0) RW Bit US
06.061 Standby Mode Mask 0000000 to 1111111 0000000 RW Bin US
06.065 Standard Under Voltage Threshold 0 to VM_STD_UNDER_VOLTS V
200 V drive: 175 V
400 V drive: 330 V
575 V drive: 435 V
690 V drive: 435 V
RW Num RA US
06.066 Low Under Voltage Threshold 24 to VM_LOW_UNDER_VOLTS V
200 V drive: 175 V
400 V drive: 330 V
575 V drive: 435 V
690 V drive: 435 V
RW Num RA US
06.067 Low Under Voltage Threshold Select Off (0) or On (1) Off (0) RW Bit US
06.071 Slow Rectifier Charge Rate Enable Off (0) or On (1) Off (0) RW Bit US
06.072 User Supply Select Off (0) or On (1) Off (0) RW Bit US
06.073 Braking IGBT Lower Threshold 0 to VM_DC_VOLTAGE_SET V
200 V drive: 390 V
400 V drive: 780 V
575 V drive: 930 V
690 V drive: 1120 V
RW Num RA US
06.074 Braking IGBT Upper Threshold 0 to VM_DC_VOLTAGE_SET V
200 V drive: 390 V
400 V drive: 780 V
575 V drive: 930 V
690 V drive: 1120 V
RW Num RA US
06.075 Low Voltage Braking IGBT Threshold 0 to VM_DC_VOLTAGE_SET V 0 V RW Num RA US
06.076
Low Voltage Braking IGBT Threshold
Select
Off (0) or On (1) Off (0) RW Bit
06.084 Date And Time Offset ±24.00 Hours 0.00 Hours RW Num US
RW Read / Write RO Read only Num Number parameter Bit Bit parameter Txt Text string Bin Binary parameter FI Filtered
ND No default value NC Not copied PT Protected parameter RA Rating dependent US User save PS Power-down save DE Destination
IP IP address Mac Mac address Date Date parameter Time Time parameter SMP Slot,menu,parameter Chr Character parameter Ver Version number