198 Unidrive M Regen Design Guide
Issue Number: 4
Figure 9-9 Menu 8 Relay output logic diagram
The drive has eight digital I/O terminals (T22, T24 to T29 and the relay) and an enable input. Each input has the same parameter structure. The digital
I/O is sampled every 2 ms, except when inputs are routed to the limit switches Pr 06.035 and Pr 06.036 when the sample time is reduced to 250 s.
Any changes to the source/destination parameters only become effect after drive reset is activated.
Table 9-10 Digital I/O
I/O Sample rate Function
T24 to T26 2 ms Digital input or output
T27 to T29 2 ms Digital input
Relay 4 ms
T22 2 ms 24 V output
Terminal type
I/O state Invert Source / destination Output select
Parameter Parameter Default Parameter Default Parameter Default
T24 input / output 1 Pr 08.001 Pr 08.011 0Pr08.021 Pr 03.009 – Synchronized Pr 08.031 1
T25 input / output 2 Pr 08.002 Pr 08.012 0Pr08.022 Pr 03.008 – Contactor closed Pr 08.032 0
T26 input / output 3 Pr 08.003 Pr 08.013 0Pr08.023 Pr 10.001 – Drive OK Pr 08.033 1
T27 input 4 Pr 08.004 Pr 08.014 0Pr08.024 Pr 10.033 – Drive reset
T28 input 5 Pr 08.005 Pr 08.015 0Pr08.025 Pr 0.000 – Not used
T29 input 6 Pr 08.006 Pr 08.016 0Pr08.026 Pr 0.000 – Not used
T41 / 42 Relay Pr 08.007 Pr 08.017 0Pr08.027 Pr 03.007 – Close contactor
T22 24 V output Pr 08.008 Pr 08.018 1Pr08.028 Pr 0.000 – Not used
T31 Safe Torque Off /
Drive enable
Pr 08.009
and
Pr 08.040
08.027
Relay
Source
08.017
Relay Source
Invert
??.???
Any bit
parameter
??.???
x(-1)
Relay
State
08.007
03 7.00
Disable Charge System /
Close Contactor
41
42
0V