EasyManua.ls Logo

Nidec Unidrive M600 Series - Page 235

Nidec Unidrive M600 Series
344 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety
information
Introduction
Product
Information
System
design
Mechanical
Installation
Electrical
Installation
Getting
started
Optimization Parameters
Technical
data
Component
sizing
Diagnostics
UL
Information
Unidrive M Regen Design Guide 235
Issue Number: 4
* Not available on Unidrive M700.
Option Synchronisation Select (11.001) is used to select and enable timing synchronisation between the communications system associated with an
option module fitted to the drive and the drive control system. If "Not Active" is selected then the drive control system operates using it's own
processor crystal for control sample timing. If one of the option modules is selected and is making a request to provide synchronisation then the drive
control sample timing will be synchronised to the communication system. Option synchronisation Active (11.002) shows the synchronisation source,
where "Not Active" indicates that the drive is providing the timing for the control system. Any other value indicates if an option module is providing
synchronisation. If required the synchronisation source can be selected automatically by setting Option Synchronisation Select (11.001) to
"Automatic". In this case the option module in the lowest numbered slot that is making a request to provide synchronisation will be selected.
See Option Synchronisation Select (11.001).
See Parameter Displayed At Power-up (11.022).
11.064 Product Identifier Characters 1295396912 to 2147483647 RO Num ND NC PT
11.065 Drive Rating And Configuration 00000000 to 99999999 RO Num ND NC PT
11.066 Power Stage Identifier 0 to 255 RO Num ND NC PT
11.067 Control Board Identifier 0.000 to 65.535 RO Num ND NC PT
11.068 Internal I/O Identifier 0 to 255 RO Num ND NC PT
11.069 Position Feedback Interface Identifier 0 to 255 RO Num ND NC PT
11.070 Core Parameter Database Version 0.00 to 99.99 RO Num ND NC PT
11.071 Number Of Power Modules Detected 0 to 20 RO Num ND NC PT US
11.072 NV Media Card Create Special File 0 to 1 0 RW Num NC
11.073 NV Media Card Type None (0), SMART Card (1), SD Card (2) RO Txt ND NC PT
11.075 NV Media Card Read-only Flag Off (0) or On (1) RO Bit ND NC PT
11.076 NV Media Card Warning Suppression Flag Off (0) or On (1) RO Bit ND NC PT
11.077 NV Media Card File Required Version 0 to 9999 RW Num ND NC PT
11.079 Drive Name Characters 1-4 -2147483648 to 2147483647 0 RW Num PT US
11.080 Drive Name Characters 5-8 -2147483648 to 2147483647 0 RW Num PT US
11.081 Drive Name Characters 9-12 -2147483648 to 2147483647 0 RW Num PT US
11.082 Drive Name Characters 13-16 -2147483648 to 2147483647 0 RW Num PT US
11.084 Drive Mode
Open-loop (1), RFC-A (2), RFC-S (3),
Regen (4)
RO Txt ND NC PT US
11.085 Security Status
None (0), Read-only (1), Status-only (2),
No Access (3)
RO Txt ND NC PT PS
11.086 Menu Access Status Menu 0 (0), All Menus (1) RO Txt ND NC PT PS
11.090 Keypad Port Serial Address 1 to 16 1 RW Num US
11.091 Additional Identifier Characters 1 -2147483648 to 2147483647 RO Num ND NC PT
11.092 Additional Identifier Characters 2 -2147483648 to 2147483647 RO Num ND NC PT
11.093 Additional Identifier Characters 3 -2147483648 to 2147483647 RO Num ND NC PT
11.095 Number Of Rectifiers Detected 0 to 9 RO Num ND NC PT
11.096 Number Of Rectifiers Expected 0 to 9 0 RW Num US
RW Read / Write RO Read only Num Number parameter Bit Bit parameter Txt Text string Bin Binary parameter FI Filtered
ND No default value NC Not copied PT Protected parameter RA Rating dependent US User save PS Power-down save DE Destination
11.001 Option Synchronisation Select
RW Txt US
Not Active (0), Slot 1 (1), Slot 2 (2), Slot 3 (3),
Slot 4 (4), Automatic (5)
Slot 4 (4)
11.002 Option synchronisation Active
RO Txt ND NC PT US
Not Active (0), Slot 1 (1), Slot 2 (2), Slot 3 (3),
Slot 4 (4)
11.018 Status Mode Parameter 1
RW Num PT US
0.000 to 59.999
0.000
Parameter Range Default Type

Table of Contents

Related product manuals