Table 10-13 Unidrive M size 10 and 11 rectifier current and fuse ratings
* Twin rectifier
Table 10-14 Cable ratings for Unidrive size 10 and 11 rectifiers
* Twin rectifier
10.3.2 Common DC bus fusing
DC bus fusing is required in the following systems for both the Regen and motoring drives, and the rectifier if used as the external soft start circuit.
1. Single Regen, multiple motoring drives
2. Multiple Regen, multiple motoring drives
3. Unidrive M Regen brake resistor replacement
4. Regen systems using a rectifier
DC bus fuses as detailed following must be fitted in both the positive and negative branches of DC bus connections to each of the Regen and
motoring drives, and the rectifier if used as the external soft start circuit.
Ferraz have a range of DC fuses which could be used to provide the required protection, types (00 and 21) may be used.
00 - Fuse with no trip indicator fitted
21 - Fuse fitted with trip indicator
The DC bus voltage set-point on a Regen system (default) is set to 700 Vdc, this can be up to a maximum 800 Vdc. Therefore ensure the selected
DC bus fusing is of the correct voltage rating with regards to the DC bus voltage level (Pr 03.005 DC Bus Voltage Set-point).
Model
Typical
input
current
Maximum
continuous
input current
Maximum
overload input
current
Fuse rating
IEC UL/USA
Nominal Maximum
Class
Nominal Maximum
Class
AA A
AA A A
10204100 333 361 494 450 450
gR
450 450
HSJ
10404520 370 396 523 450 450 450 450
10502430 202 225 313 250 250 250 250
10602480 202 225 313 250 250 250 250
11406840 502 539 752 630 630
gR
600 600
HSJ
11503840 313 338 473 400 400 400 400
11604060 298 329 465 400 400 400 400
1142X400* 2 x 326 2 x 358 2 x 516 400 400 400 400
1162X380* 2 x 308 2 x 339 2 x 488 400 400 400 400
Model
Cable size (IEC) Cable size (UL)
mm²
AWG or kcmil
Input
Output Input Output
Nominal Maximum
Installation
method
Nominal Maximum
Installation
method
Nominal Maximum Nominal Maximum
10204100 2 x 150 2 x 185 C 2 x 120 2 x 150 C 2 x 300 2 x 500 2 x 400 2 x 500
10404520 2 x 150 2 x 185 C 2 x 150 2 x 150 C 2 x 350 2 x 500 2 x 500 2 x 500
10502430 2 x 95 2 x 185 B2 2 x 95 2 x 150 B2 2 x 3/0 2 x 500 2 x 3/0 2 x 500
10602480 2 x 95 2 x 185 B2 2 x 95 2 x 150 B2 2 x 3/0 2 x 500 2 x 3/0 2 x 500
11406840 4 x 120 4 x 120 C 4 x 150 4 x 150 C 2 x 250 2 x 250 2 x 300 2 x 300
11503840 2 x 120 2 x 120 C 2 x 120 2 x 120 C 2 x 250
11604060 2 x 120 2 x 120 C 2 x 120 2 x 120 C 2 x 300 2 x 300 2 x 400 2 x 400
1142X400* 2 x 2 x120 2 x 2 x120 C 2 x 2 x 120 2 x 2 x 120 C 2 x 2 x 300
1162X380* 2 x 2 x120 2 x 2 x120 C 2 x 2 x 120 2 x 2 x 120 C 2 x 2 x 300