Issue Number: 4
Table 10-25 400 V (380 V to 480 V ±10 %) Regen filter components to support up to 2 % THD
v
on grid
* Modify Rated Current (05.007) to match current rating of inductor.
Drive mode Regen inductor SFF inductor SFF capacitor
Heavy
Duty
Normal
Duty
mH Arms Part number mH Arms Part number
Capacitor
value
Rated
voltage
Part
number
Capacitor
current
per can
Fuse
rating
(A)
µF Vac Arms
03400078 03400078*
6.300 9.5 4401-0405 3.160
9.5
4401-0162
8
525
1610-7804
3.3
6
03400100* 9.5
6
03400100* 5.000 12 4401-0406 2.500 12 4401-0163
6
04400150 04400150*
3.750 16 4401-0407 1.875 16 4401-0164 3.5
6
04400172*
6
05400270* 04400172 2.400 25 4401-0408 1.200 25 4401-0165 4.1
6
05400300 05400270
1.760 34 4401-0409 0.880 34 4401-0166
32 1665-8324
13
20
06400350* 05400300
20
06400420* 06400350 1.500 40 4401-0410 0.750 40 4401-0167 13.1
20
06400470* 06400420* 1.300 46 4401-0411 0.650 46 4401-0168 13.3
25
06400470* 1.000 60 4401-0412 0.500 60 4401-0169 13.9
25
07400660 07400660* 0.780
74 4401-0413 0.390 77 4401-0170 14.8
25
07400770* 0.780
25
07401000* 07400770 0.630 96 4401-0414 0.315 96 4401-0171
39 1665-8394
18.1
32
08401340* 07401000 0.480 124 4401-0415 0.240 124 4401-0172 20.1
32
08401570* 08401340 0.380 156 4401-0416 0.190 156 4401-0173 22.7
40
08401570* 0.330 180 4401-0417 0.165 180 4401-0174 24.8
40
09402000* 09402000*
0.300 202 4401-0418 0.135 200 4401-0175
2 x 39
2 x
1665-8394
18.4
32
09402240*
32
10402700 09402240
0.200 300 4401-0419 0.100 300 4401-0176 20.1
32
10403200* 10402700*
32
10403200* 0.168 350 4401-0420 0.080 350 4401-1205 25.4
40
11403770 11403770
0.135 437 4401-0292 0.067 437 4401-0301
3x 64
3 x
1665-8644
33.5
50
11404170
50
11404640
50
11404170
0.121 487 4401-0293 0.060 487 4401-0302
50
11404640
50