Safety
information
Introduction
Product
Information
System
design
Mechanical
Installation
Electrical
Installation
Getting
started
Optimization
Parameters
Technical
data
Component
sizing
Diagnostics
UL
Information
302 Unidrive M Regen Design Guide
Issue Number: 4
Table 10-41 575 V / 690 V SFF inductor specifications
Switching frequency filter inductors
The following inductors are standard 3-phase inductors. They carry only 50/60 Hz current with a negligible amount of high frequency current.
The switching frequency filter inductors need to be rated to the total current requirement of the system.
10.4.8 Switching frequency filter capacitors
Switching frequency filter capacitor specification
Overload - I
max
= 1.3 x I
rated
I
inrush
= 200 x I
rated
Inductor part
number
Amps mH
Losses L D H Weight Fixing centres (x * y) Fixing
Fixing type
Wmmmmmmkg mm mm
4401-1211 22 1.400 36 190 120 180 10 130 x 74 8 x 20
B
4401-1213 36 1.400 81 255 160 240 16 200 x 80 10 x 20
4401-1214 43 1.200 86 255 170 240 20 200 x 90 10 x 20
4401-1215 52 1.000 93 255 180 240 22 200 x 100 10 x 20
4401-1216 63 0.800 95 255 190 240 25 200 x 100 10 x 20
4401-1217 85 0.600 122 300 180 300 37 204 x 113 10 x 20
4401-1218 100 0.500 190 300 180 300 37 204 x 120 4 x 10
4401-1219 125 0.400 172 300 190 300 49 204 x 123 10 x 20
4401-1220 144 0.350 177 300 200 300 50 204 x 130 10 x 20
4401-1221 168 0.300 207 300 200 300 50 204 x 130 10 x 20
4401-1222 192 0.260 220 325 220 325 55 204 x 160 4 x 10
4401-1223 192 0.210 189 300 200 300 50 204 x 130 10 x 20
4401-0306 230 0.221 357 360 176 322 58 328 x 263 11 x 17 A
4401-0307 281 0.181 375 360 176 322 66 328 x 263 11 x 17 A