Unidrive M Regen Design Guide 307
Issue Number: 4
Table 10-49 Combi filter ratings
Table 10-50 Combi filter SFF component values
Table 10-51 Combi filter leakage current
* SFF caps wired in Delta configuration
** In accordance with IEC 60939-1
The range of combi filters covered in this section are available from Schaffner, the filters are not stocked by supplier of the drive.
Schaffner model number
Current rating Voltage rating Rated frequency
AVac Hz
FS6085-83-35-2 83 480 50/60
FS6085-125-35-2 125 480 50/60
FS6085-168-40-2 168 480 50/60
FS6085-205-40-2 205 480 50/60
FS6085-300-99-2 300 480 50/60
FS6085-350-99-2 350 480 50/60
FS6085HV-200-40-2 200 690 50/60
Schaffner model number
Component values Losses
SFF Ind uH
SFF Cap uF
*
W
FS6085-83-35-2 84 3 x 20 98
FS6085-125-35-2 70 3 x 30 92
FS6085-168-40-2 44 3 x 40 133
FS6085-205-40-2 40 3 x 50 133
FS6085-300-99-2 25 3 x 80 180
FS6085-350-99-2 20 3 x 80 235
FS6085HV-200-40-2 63 3 x 90 120
Schaffner model number
Ground leakage
Balanced supply (mA)
**
Worst case (mA)
FS6085-83-35-2 4.3 220
FS6085-125-35-2 12.5 619
FS6085-168-40-2 4.3 221
FS6085-205-40-2 12.5 631
FS6085-300-99-2 12.5 636
FS6085-350-99-2 12.5 636
FS6085HV-200-40-2 16.5 820
Combi filters listed in Table 3-23 Combi filter selection on page 39 are equipped with an internal thermal switch to prevent the EMC filter
inductor from overheating. The thermal switch must be configured to open the main supply contactor in the event of a thermal overload.
NOTE
WARNING
Regen inverter output current derating must be applied where necessary based on Regen inductor and combi filter capability.
Models affected are denoted with * in Table 3-23 Combi filter selection on page 39. Combi filters listed in Table 3-23 are suitable for use in
systems with less than 2 % THD
v
on the grid.