Safety
information
Introduction
Product
Information
System
design
Mechanical
Installation
Electrical
Installation
Getting
started
Optimization
Parameters
Techn i c al
data
Component
sizing
Diagnostics
UL
Information
Unidrive M Regen Design Guide 321
Issue Number: 4
Derivative Image Derivative Image error
248
The Derivative Image trip indicates that an error has been detected in the derivative image. The sub-trip number indicates
the reason for the trip.
Recommended action:
Contact the supplier of the drive
Destination Two or more parameters are writing to the same destination parameter
199
The Destination trip indicates that destination output parameters of two or more logic functions (Menus 5, 7, 8, 9, 12 or 14)
within the drive are writing to the same parameter.
Recommended actions:
•Set Prmm.000 to ‘Destinations’ or 12001 and check all visible parameters in all menus for parameter write conflicts
Drive Size Power stage recognition: Unrecognized drive size
224
The Drive Size trip indicates that the control PCB has not recognized the drive size of the power circuit to which it is
connected.
Recommended action:
• Ensure the drive is programmed to the latest firmware version
• Hardware fault - return drive to supplier
Trip Diagnosis
Sub-trip Reason Comments
1 to 52
An error has been detected in the derivative image,
contact the supplier of the drive.
61
The option module fitted in slot 1 is not allowed with
the derivative image
Occurs when the drive powers-up or the image
is programmed. The image tasks will not run.
62
The option module fitted in slot 2 is not allowed with
the derivative image
63
The option module fitted in slot 3 is not allowed with
the derivative image
64
The option module fitted in slot 4 is not allowed with
the derivative image
70
An option module that is required by the derivative
image is not fitted in any slot
Occurs when the drive powers-up or the image
is programmed. The image tasks will not run.
71
An option module specifically required to be fitted in
slot 1 not present
72
An option module specifically required to be fitted in
slot 2 not present
73
An option module specifically required to be fitted in
slot 3 not present
74
An option module specifically required to be fitted in
slot 4 not present
80 to 81
An error has been detected in the derivative image,
contact the supplier of the drive.