Safety
information
Introduction
Product
Information
System
design
Mechanical
Installation
Electrical
Installation
Getting
started
Optimization Parameters
Technical
data
Component
sizing
Diagnostics
UL
Information
Unidrive M Regen Design Guide 37
Issue Number: 4
Table 3-20 575 V (500 V to 575 V ±10 %) Regen filter components to support up to 2 % THD
v
on grid
* Modify Rated Current (05.007) to match current rating of inductor.
*** Delta connection
Drive mode Regen inductor SFF inductor SFF capacitor
Heavy
Duty
Normal
Duty
mH Arms Part number mH Arms
Part
number
Capacitor
value
Rated
voltage
Part
number
Capacitor
current
per can
Fuse
rating
(A)
µF Vac Arms
06500150 06500150
5.300 19 4401-0210
1.400
22 4401-1211
11.2
690
1666-8113
5.2
8
06500190 8
06500230* 06500190 4.600 22 4401-0211 8
06500290* 06500230 3.800 27 4401-0212 36 4401-1213 5.3 8
06500350 06500290 2.800 36 4401-0213 1.200 43 4401-1214 5.6 10
07500440* 06500350 2.400 43 4401-0214 1.000 52 4401-1215 5.9 10
07500550* 07500440* 1.900 52 4401-0215 0.800 63 4401-1216 6.4 10
08500630 07500550* 1.600 63 4401-0216 0.600 85 4401-1217 6.9 12
08500860* 08500630* 1.200 85 4401-0217 0.510 100 4401-1218 8.2 16
09501040* 08500860* 1.000 100 4401-0218 0.400 125 4401-1219
22.5 1666-8223
12.5 20
09501310* 09501040 0.810 125 4401-0219 0.350 144 4401-1220 13.8 25
10501520* 09501310* 0.700 144 4401-0220 0.300 168 4401-1221 14.9 25
10501900 10501520*
0.530 192
4401-0421
0.210 192
4401-1223
2 x 22.5
2 x
1666-8223
12.2
20
10501900* 4401-0421 4401-1223 20
11502000 0.441 230 4401-0297 0.221 230 4401-0306 2 x 46.2***
800
2 x
1668-8464
24
40
11502000 0.361 281 4401-0298 0.181 281 4401-0307 3 x 46.2***
3 x
1668-8464
40
11502540 0.441 230 4401-0297 0.221 230 4401-0306 2 x 46.2***
2 x
1668-8464
40
11502540 0.361 281 4401-0298 0.181 281 4401-0307 3 x 46.2***
3 x
1668-8464
40
11502850 0.441 230 4401-0297 0.221 230 4401-0306 2 x 46.2***
2 x
1668-8464
40
11502850 0.361 281 4401-0298 0.181 281 4401-0307 3 x 46.2***
3 x
1668-8464
40