Table 4-4 Key to Figure 4-7
Key Description Key Description
L1, L2, L3 Three phase supply Aux.2b K2 NC auxiliary contact Regen 1
F1, F2, F3 Main Regen system supply AC fuses Aux.2c K2 NC auxiliary contact Regen 1
F4, F5, F6 Regen drive 1 AC fuses Aux.3 K3 NC auxiliary contact
F7, F8, F9 Regen drive 2 AC fuses Aux.4a K4 NO auxiliary contact Regen 2
F13, F14 DC Bus fusing to rectifier Aux.4b K4 NC auxiliary contact Regen 2
F15, F16, F17, F18 DC Bus fusing to Regen drives Aux.4c K4 NC auxiliary contact Regen 2
F19, F20, F21, F22 DC Bus fusing to motoring drive
Rly.1
Optional isolation for enable between Regen and motoring
drive(s)
VDR1, 2, 3 Varistor network line-to-line
VDR4, 5, 6 Varistor network line-to-ground Mt.1 Motor thermistor 1
EMC Optional EMC filter Mt.2 Motor thermistor 2
L1 Switching frequency filter inductor Tc.1 Regen inductor thermistor
L2 Regen inductor (Regen 1) +DC, -DC Motoring drive power connection to Regen drive
L3 Regen inductor (Regen 2) S1 Regen drive enable
CBA 1 Switching frequency filter capacitor bank A (Regen 1) S2 Motoring drive enable
CBB 1 Switching frequency filter capacitor bank B (Regen 1) S3 Motoring drive reset
CBA 2 Switching frequency filter capacitor bank A (Regen 2) S4 Motoring drive run forward
CBB 2 Switching frequency filter capacitor bank B (Regen 2) S5 Motoring drive run reverse
K1 Main supply contactor S6 Regen drive reset (user programmed)
K2 Regen drive 1 main contactor TPR1 Thermal protection relay
K3 Charging contactor Vsupply System control supply
K4 Regen drive 2 main contactor
F26, F27, F28, F29,
F30, F31
Optional switching frequency filter capacitor fuses
Aux.2 OPD2 NO auxiliary contact
Aux.2a K2 NO auxiliary contact Regen 1
Regen inductor thermistor must be configured to disable the drive in the event of a thermal overload. The switching frequency filter inductor