Unidrive M Regen Design Guide 69
Issue Number: 4
Table 4-13 575 V Regen system maximum cable length
Table 4-14 690 V Regen system maximum cable length
If the cable length in the above tables are exceeded, additional components are required. Refer to section 4.6.1 Available preventative measures on
page 72.
4.5.1 Cable type
Use 105 °C (221 °F) (UL 60/75 °C temp rise) PVC-insulated cable with copper conductors having a suitable voltage rating, for the following power
connections:
• AC supply to external EMC filter (when used)
• AC supply (or external EMC filter) to Regen drive
• Regen drive to motoring drive (or busbar arrangement could be used)
• Motoring drive to motor
Model
575 V Nominal AC supply voltage
Maximum permissible cable length
Motoring drive switching frequency
3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
05500030
200 m (660 ft) 150 m (490 ft) 100 m (330 ft) 75 m (245 ft) 50 m (165 ft) 37 m (120 ft)
05500040
05500069
06500100
06500150
06500190
06500230
06500290
06500350
07500440
250 m (820 ft) 187 m (614 ft)
125 m (410 ft) 93 m (305 ft) 62 m (203 ft) 46 m (151 ft)
07500550
08500630
08500860
09501040
09501310
10501520
10501900
11502000
11502540
11502850
Model
690 V Nominal AC supply voltage
Maximum permissible cable length
Motoring drive switching frequency
3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
07600190
250 m (820 ft) 187 m (614 ft)
125 m (410 ft) 93 m (305 ft) 62 m (203 ft) 46 m (151 ft)
07600240
07600290
07600380
07600440
07600540
08600630
08600860
09601040
09601310
10601500
10601780
11602100
11602380
11602630