Operating Parameters
B-6
Part 1120277_01
E 2012 Nordson Corporation
Standard (contd)
13 Change Hose 2 Output to Electric Gun Activation
Description: Changes the proportioned 240 VAC current that is provided to
the hose 1 heater to a switched 240 VAC current that is used to
activate a manifold-mounted electric gun.
Value: 0(disabled)
1(enabled)
Resolution:
Default Value: 0(disabled)
Format:
Use: Use only when a Nordson manifold-mounted electric gun is
installed and a switching device is connected to the melter's
switch receptacle. Refer to the electric gun manual for
information on mounting and using the gun.
14 External Communications Lock-out
Description: Used as a safety feature when performing maintenance on the
melter. Prevents external control of the melter through st andard
or optional inputs/outputs or network communications (optional)
Value: 0(disabled)
or
1(enabled)
Resolution:
Default Value: 0(disabled
Format:
Use: Set parameter to 1 (enabled) before performing any
maintenance on the melter. When enabled, all external control of
the melter stops until the parameter is once again set to 0
(disabled).