EasyManua.ls Logo

Notifier 1010

Notifier 1010
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PAGE 26 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
WIRING CONTROL MODULES (CMX-2)
CMX-2’s are used for Bells, Solenoids or any general relay application and can be monitored
outputs or relay outputs.
WIRING SHORT CIRCUIT ISOLATOR MODULES (ISO-X)
Note: When using
the ISO-X module,
limit the devices
between each ISO-X
to 25 devices.
In the case of “T”
taping the limit of 25
also applies.
The ISO-X doesn’t
affect the device
count unless the
amount of ISO-x’s
exceeds 100

Table of Contents

Related product manuals