PAGE 26 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
WIRING CONTROL MODULES (CMX-2)
CMX-2’s are used for Bells, Solenoids or any general relay application and can be monitored
outputs or relay outputs.
WIRING SHORT CIRCUIT ISOLATOR MODULES (ISO-X)
Note: When using
the ISO-X module,
limit the devices
between each ISO-X
to 25 devices.
In the case of “T”
taping the limit of 25
also applies.
The ISO-X doesn’t
affect the device
count unless the
amount of ISO-x’s
exceeds 100