EasyManuals Logo
Home>Notifier>Security System>1010

Notifier 1010 User Manual

Notifier 1010
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
1010/2020 INSTALLATION AND PROGRAMMING MANUAL PAGE 29
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
DIP-SWITCH SETTINGS
The following section indicates the typical Dip-switch settings for Annunciators (SCS-8, ACM-16AT,
ACM-8R, ACM-32A, LDM-32, LDM-32R, LCD-80 and LCD-80TM)
SETTING ANNUNCIATOR BOARD ADDRESSES:
Typical Annunciator address selection method
The first decimal dial on the left-hand side selects the address in unit of ten, the second dial selects
the address in units of one.
SCS-8 FAN CONTROL MODULE ANNUNCIATOR
SW ON OFF
1 –10sec to duct detector latching time
(Standard time = 60 Seconds)
No Change
2 –20sec to duct detector latching time
(Standard time = 60 Seconds, )
No Change
3 Instant Fan Faults Fan Faults Delayed 30 Sec
4 Addresses 33-64 Are ALL additional
latching fire trips.
Addresses 33-63 are for SCE-8
Address 64 is the only FTR.
5 Global mode Reset Activated ie: Broadcast
latching plant trip reset to all SCS-8’s
Global Mode Reset Disabled: Ie:
plant trip reset restricted to current
SCS-8.
6 Latching A/C Trip Non-Latching A/C Trip
7* Fire Mode LED From Z240. Fire Mode Led, from Common Alarm
LED.
8 EOL Resistor for RS485 EOL resistor out of circuit.
* With the SCS-8 there is a choice as to how a Fire Mode trip is activated.
Dip Switch 7 when ON- selects Z240 as the input to the SCS-8 to activate Fire Mode.
Dip Switch 7 when OFF- selects the common alarm LED as the input for the SCS-8 Fire Mode Trip.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier 1010 and is the answer not in the manual?

Notifier 1010 Specifications

General IconGeneral
BrandNotifier
Model1010
CategorySecurity System
LanguageEnglish

Related product manuals