PAGE 64 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
ADDRESSABLE DETECTORS
Type I.D. Display Label Type of Device
ION
CMBO
PHOT
THER
PHOD
SMOKE (ION)
SMOKE(COMBO)
SMOKE(PHOTO)
HEAT(ANALOG)
PHOT(DUCT)
CPX-/751 Intelligent Ionisation Smoke
Detector.
IPX/751 Intelligent Combination
Ion/Photo/Thermal Smoke Detector (Omni)
SDX-551/751 Intelligent Photoelectric Smoke
Detector.
FDX-551 or FDX-551R Intelligent Thermal
Sensor.
SDX-551/751 Intelligent Photoelectric Smoke
Detector.
When being used as a DUCT PROBE in
AS1668 fan applications. The PHOD type ID
behaves as a security type input, displays on
the LCD but does not trip a general alarm
condition.
ALARM INITIATION MODULES
Type I.D. Display Label Type of Device
MON
NONA
SCON
SPSU
SUPR
MONITOR
NON ALM MON
SMOKE (CONV)
SPRINKLER MNTR
SUPERVISORY
MNTR
MMX Monitor Module or an XP5-M used to
monitor normally open contacts, (ie. break
Glass Alarms,).
MMX Monitor Module or an XP5-M used to
monitor Pump indications or tamper switches,
and display them on an ACM32-A, This Type
does not indicate on the LCD display and will
not initiate a fire alarm condition:
MMX-2 Monitor Module used to monitor
conventional 2-wire smoke detectors. This
module has a longer reset period than modules
programmed as MON. (Also allows AVF)
MMX 101 Monitor module used to monitor Flow
switches,
This type indicates on the display and has CBE
but does not activate an alarm condition.
(Tracking is active for this device)
MMX 101 Monitor Module used to monitor any
Tamper Input that is required to display on the
DIA, without operating an Alarm condition
(Tracking is an option for this device)