1010/2020 INSTALLATION AND PROGRAMMING MANUAL PAGE 69
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
A FAN THAT STOPS IN FIREMODE, WITH ASSOCIATED DUCT DETECTOR.
Address Type Label Annunciator Map
L1M1 FRCM FAN START A1P1
L1M2 FRCM FAN STOP A1P2
L1M3 NONA FAN STATUS A1P3
L1D4 PHOD DUCT PROBE A1P4
FIRE TRIP RELAY
A fire trip relay is configured as follows
Address Type Label Annunciator
Map*
CBE
L1M1 FRCM FTR A1P64 OR (Z200 )
* If the dip-switch on the SCS-8 is set for extra latching fire trips, then addresses A1P33-A1P64 can
also be used.