1010/2020 INSTALLATION AND PROGRAMMING MANUAL PAGE 41
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
ISIB (8=ISIB)
Option 8 allows the changing of any of the following:
Intelligent SIB Allows you to add or delete the ISIB and set the network address.
ANN Add or Delete Annunciators Boards.
XINT When activated allows Upload/Download through Verifire. This will
disconnect the Annunciators RS485 stream to be dedicated to
UP/DL. Repeat to return too normal once UP/DL complete.
UDACT Not Used in Australia.
ADDITIONAL SYSTEM PARAMETERS (9=PARM)
This option allows the programmer to de-activate/activate the following:
High Day/Night Zone Allows you to set detector sensitivity for High see Note below *.
Low Day/night Zone Allows you to set detector sensitivity for Low see Note below *.
Detector Verification
Counter
This option resets the counter that records the number times a
detector went into AVF without alarming.
SACM/SAQM Reporting Not Used In Australia.
Drift Compensation When selected the Panel automatically adjusts the detectors to
the environmental condition of the surroundings, within certain
parameters, see Note below **.
Pager Programming Activate if Pager Interface installed.
Modem Programming Activate if Modem installed.
NAM Programming Activate if Network Annunciator Module installed.
Rapid Polling Sets first 20 modules on each loop to poll at double the rate,
providing faster response. (ie: Manual Call Points, Bell Outputs)
ACS Reporting If activated Any input module with a supervisory type ID, will
indicate state changes on an Annunciator as a red LED.