PAGE 38 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
TIME DELAYS (3=TDLY)
Option 3 allows the programmer to activate or de-activate Alarm Verification of Analog Addressable
detectors, as well as setting the appropriate time delays for this function.
Note: MMX-2 modules AVF is hard coded at 20 seconds.
The following programming example illustrates enabling the AVF function:
From the Partial System programming menu, select 3=TDLY:
DO YOU WANT TO CHANGE THE DETECTOR VERIFICATION TIME?.
Y
DO YOU WANT THE DETECTOR VERIFICATION TIME ACTIVATED? Y
ENTER THE DETECTOR VERIFICATION TIME. 20
This sets the global parameters for the System, eg; 20 second time on AVF. When installing each
detector you are required to select if you want AVF or not.
DO YOU WANT TO SET THE BELL-ISOLATE INHIBIT TIME?.
N
SELECT TIME
DO YOU WANT TO SET THE BELL CUTOFF TIME?.
Y
SELECT TIME 600
Bell Isolate Inhibit time is the period of time after the first alarm that the Bell Isolate key is disabled.
We recommend this function not be used, unless there are special circumstances.
Answer NO to disable function. Range = 0-240 seconds.
Bell Cut-Off time is for the automatic isolation of bells X seconds after an alarm.
We recommend this function not be used, unless there are special circumstances.
Answer NO to disable function. Range = 0-2040 seconds.
Please note that if bell cut-off is set, the EXT BELL ISOL state will remain latched on until a system
reset is performed, normal toggle on/off will then resume.
Please note, both Bell Cut-Off & Inhibit functions are global and will apply to all devices marked with
the “bell-isolate” flag.
Please refer to BCA and Standard requirements for your application.
AUDIO VISUAL POWER SUPPLIES (4=AVPS)
4=AVPS -Not Used in Australia.