EasyManuals Logo
Home>Notifier>Security System>1010

Notifier 1010 User Manual

Notifier 1010
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
1010/2020 INSTALLATION AND PROGRAMMING MANUAL PAGE 67
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
ANNUNCIATOR ZONE
Type I.D. Display Label Type of Device
AZON
AACT
AGZN
ANN ZONE
ALM ACTIVATE
ANN GLOBAL ZON
Annunciator Point, In the case of an ACM-
16at, AZON acts as a Zone Isolate Facility, or
can be used to isolate a module, and will
display an alarm state if the point isolated is in
alarm.
Annunciator Point, when using an ACM 16AT,
AACT is used to activate a zone.
Annunciator Point, when using an ACM16AT,
AGZN is used to isolate all inputs to any
Forward Zone associated with this Type ID. The
zone needs to be the First zone in the CBE for
an input device.
ANNUNCIATOR INPUT
Type I.D. Display Label Type of Device
AINP ANN INPUT Annunciator Point that indicates the state of
any input mapped to it. (Zone Module or
Detector)
It does not display an alarm, if the device is
isolated.
ANNUNCIATOR OUTPUT
Type I.D. Display Label Type of Device
ACON
AFCM
ANN CONTROL
ANN FORC MAN
Annunciator Point that can be used for
manual control of relays to activate solenoids
on sprinkler installations, it also indicates the
state of any CMX Control Module, or XP5-C
relay mapped to it.
Annunciator Point Used for fan controls
Start/Stop, that is not deactivated upon system
reset, and similar applications only with an
FRCM control device.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier 1010 and is the answer not in the manual?

Notifier 1010 Specifications

General IconGeneral
BrandNotifier
Model1010
CategorySecurity System
LanguageEnglish

Related product manuals