ANNUNCIATOR ZONE
Type I.D. Display Label Type of Device
AZON
AACT
AGZN
ANN ZONE
ALM ACTIVATE
ANN GLOBAL ZON
Annunciator Point, In the case of an ACM-
16at, AZON acts as a Zone Isolate Facility, or
can be used to isolate a module, and will
display an alarm state if the point isolated is in
alarm.
Annunciator Point, when using an ACM 16AT,
AACT is used to activate a zone.
Annunciator Point, when using an ACM16AT,
AGZN is used to isolate all inputs to any
Forward Zone associated with this Type ID. The
zone needs to be the First zone in the CBE for
an input device.
ANNUNCIATOR INPUT
Type I.D. Display Label Type of Device
AINP ANN INPUT Annunciator Point that indicates the state of
any input mapped to it. (Zone Module or
Detector)
It does not display an alarm, if the device is
isolated.
ANNUNCIATOR OUTPUT
Type I.D. Display Label Type of Device
ACON
AFCM
ANN CONTROL
ANN FORC MAN
Annunciator Point that can be used for
manual control of relays to activate solenoids
on sprinkler installations, it also indicates the
state of any CMX Control Module, or XP5-C
relay mapped to it.
Annunciator Point Used for fan controls
Start/Stop, that is not deactivated upon system
reset, and similar applications only with an
FRCM control device.