PAGE 36 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
PARTIAL SYSTEM PROGRAMMING
Option 1 from the Main Programming menu allows the programmer to change the programming of
system-wide functions such as Alarm Verification of detectors, enabling Rapid Polling, and enabling
supervision of peripheral equipment in the system, Additional system parameters, such as the
number of Loops, Annunciators and ISIB in the system. Loops can also be changed in Partial
System Programming.
After selecting option 1 from the Main Programming menu, the display will show the Partial System
Programming submenu:
PRESS.1=INST, 2=STY, 3=TDLY, 4=AVPS, 5=ZBND, 6=EXTEQ, 7=LOCP, 8=ISIB, 9=PARM...
The Partial System Programming submenu has nine options, where:
Option Description
1=INST Installation – Installation or removal of the Loop Interface Boards from memory.
2=STY Style - Changing (in memory) loops wiring style 6 or 4.
3=TDLY Time Delays - Setting the time delays for Alarm Verification, Bell cutout etc.
4=AVPS Not Used in Australia.
5=ZBND Zone Boundary - Setting the zone boundary for the software memory map.
6=EXTEQ External Equipment - Changing the external equipment options, such as electrical
supervision of the Graphics Monitor.
7=LOCP Local Parameters - Setting local parameters, of Loop devices, and Loop local
mode.
8=ISIB Intelligent Serial Interface Board - Installation or removal of the Intelligent Serial
Interface Board (SIB-2048A or SIB-NET) or Annunciator modules, Also used for
setting ACS port for Upload/Download with Verifire.
9=PARM Additional System Parameters – Selection of additional system parameters such
as the detector day/night sensitivity settings, rapid polling, etc.
0=CONT Continued …….
Subsequent option is 1=IDO, “International Display Option”
Notes
When removing loop interface boards, all installed points on the affected LIBs are automatically
removed upon cycling power to the system. Programming information for installed points can be
stored in a Verifire™ database prior to removal of the LIB. Use of the Verifire™ application for the
reprogramming of previously removed points is highly recommended.
When removing Annunciator modules, all installed points on the affected Annunciators must be
removed first for proper system operation.