PAGE 52 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
REMOVING A DEVICE (5=REMV)
Option 5 from the Programming Menu allows the programmer to remove (from control panel
memory) Loop devices, software-defined zones or Annunciator points. The devices can still be
installed in the system, but the 1010/2020 will stop looking for these devices by not POLLING them.
• Devices that are removed will not function until reinstalled under Full Point Programming.
CAUTION - devices that have had their LEDs latched ON must be returned to their normal state
before removal (execute System Reset for detectors or control OFF for modules).
• Unacknowledged points must be acknowledged prior to removal.
The programming example below illustrates the screen prompts during removal of a Loop device
(smoke detector 34 on Loop 10).
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT REMOVAL
(BCKSPC TO ABORT)
L10D34
CHANGING THE PASSWORD (6=PSWD)
Option 6 from the Programming Menu allows the programmer to change the password for the
1010/2020.
Select option 6 from the main programming menu, the following screen will appear.
ENTER.PASSWORD *****
Enter your new 5-digit password.
You are only required to enter the new password once and it then becomes effective immediately.
You must ensure you do not make any errors during entry, you can use the backspace key during
entry if you have made a mistake.
A FORGOTTEN PASSWORD?
If an incorrect password is typed in to enter programming mode, the panel will respond by displaying
a special code word and prompt the programmer to re-enter the password. If the password has
been forgotten, record this code word and contact Notifier/Inertia. After proper authentication and a
fee, the password can be deciphered from the code word. Passwords will only ever be supplied to
the owners of the system.
CHANGING THE “ALL SYSTEMS NORMAL” MESSAGE (7=MSG)
Option 7 from the Programming Menu allows the programmer to change the 40-Character Custom
User Label for the system. Acceptable characters for the label include Letters A though Z, digits 0
through 9, periods (.), dashes (-), and spaces.
ENTER 40 CHARACTER CUSTOM USER LABEL NOTIFIER DEMO ROOM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier 1010 and is the answer not in the manual?

Notifier 1010 Specifications

General IconGeneral
BrandNotifier
Model1010
CategorySecurity System
LanguageEnglish

Related product manuals