PAGE 42 1010/2020 INSTALLATION AND PROGRAMMING MANUAL
COPYRIGHT © 2000, NOTIFIER INERTIA PTY LTD
DAY/NIGHT SENSITIVITY
The function Day/Night sensitivity- gives the operator the option of having the detectors high
sensitivity during certain times, or set to low sensitivity during other times. In the case of Nursing
homes or Apartment buildings when the occupants are asleep, the detectors can be placed into
high sensitivity at night. This feature overrides the normal sensitivity selection of the detectors for
that period of time, and shows the symbol SH in the read status screen of the particular detector.
The Day/Night high and low sensitivity zones may be individually activated by control-by-event
(CBE) equations written for this purpose through the use of TIM( ) equations.
The global function can be activated or de-activated in both Full and Partial System Programming.
The operator can then enable or disable this function for each individual detector.
The following must be performed when programming Day/Night Detector Sensitivity:
• Enable the Day/Night Sensitivity and set the High and Low zone numbers. This is a global
setting.
• Set the timing C.B.E for High and for Low timing activation.
• Select Day/Night Sensitivity for each individual detector.
Example: Set Loop 1 detector 1 (L1D1) for high sensitivity between 11pm and 5am 7 days a
week. To do this, follow the next three steps.
(The example assumes that L1D1 is already installed and Day/Night not Activated).
Step 1: Setup High Sensitivity Zone
Programming a Reverse zone for High Sensitivity selection
Press Program Button and enter password *****
Enter Full point Programming 4=FPGM 4
ENTER LXX(D/M)YY ZXXX OR AXXPYY FOR PT. INSTALL Z100
ENTER TYPE ID RZON
ENTER CONTROL BY EVENT
(Enter exactly as shown in the example)
TIM(SU MO TU WE TR
FR SA 23.00 05.00)
ENTER COPERATIVE CONTROL BY EVENT ( )
ENTER 20 CHARACTER CUSTOM LABEL HIGH SENSITIVITY
DO YOU WANT THIS POINT MAPPED TO AN Annunciator (YES/NO) NO
Now press backspace to go back to program mode. Backspace
Step 2: Enable Day/Night Feature
Activating Day/Night Sensitivity on the Panel
Press Program Button and enter password *****
Enter Partial System Programming 1=PSYS 1
Enter Parameters 9=PARM 9
DO YOU WANT TO CHANGE THE HIGH DAY/NIGHT SENSITIVITY
ZONE (YES/NO)
YES
DO YOU WANT A HIGH SENSITIVITY ZONE YES
ENTER HIGH DAY/NIGHT SENSITIVITY ZONE Z100
DO YOU WANT TO CHANGE THE LOW DAY/NIGHT SENSITIVTY
ZONE (YES/NO)
NO
The Display will now ask you eight additional questions, relating to other then Day/Night
Sensitivity, Answer appropriately.
Now press backspace to go back to programming mode. Backspace