How to Operate the Control Panel with a Security Alarm
+RZ WR 2
HUDWH WKH &RQWURO 3DQHO
AFC-600 Operations PN 51033:A 3/8/99 23
+RZWR5HV
RQGWRD6HFXULW
$ODUP
A
SECURITY
Type Code latches the control panel. To return the control panel to normal
operation, you must correct the condition causing the tamper, then reset the control
panel. If the control panel indicates an active
TAMPER
point, take the following action:
1RWH
,I D ILUH DODUP H[LVWV DQG
WKHUH DUH VLOHQFHG DODUPV WKH
$/$50 6,/(1&('
/(' LV OL
KWHG
D6X
HUYLVRU
DODUP ZLOO UHVRXQG
WKH
DQHO VRXQGHU
1. Press the
ACKNOWLEDGE
/
STEP
key to silence the panel sounder and switch the
SECURITY
LED from flashing to steady—regardless of the number of troubles,
alarms, and security signals. The control panel sends a Security message to the
History buffer and installed printers, terminal mode LCD-80s, and CRT-2s.
2. Correct the condition that activated the Security point.
3. When you finish correcting the Security condition, press the
SYSTEM
RESET
key to
return the control panel to normal operation (indicated by the “All Systems
Normal” message). The control panel sends an “All Systems Normal” message to
the LCD display, History buffer, and installed printers, terminal mode LCD-80s,
and CRT-2s.
Technical Manuals Online! - http://www.tech-man.com