How Special System Timers Operate
34 AFC-600 Operations PN 51033:A 3/8/99
+RZ6SHFLDO6\VWHP7LPHUV2SHUDWH
:KDWDUH6
\
VWHP7LPHUV"
The control panel provides three special system timers, programmed in the System
Function screen. Figure 28 shows a sample System Function Selection screen with
system timer settings. For instructions on changing system functions, refer to the AFC-
600 Programming Manual.
+RZWR9LHZ6
\
VWHP7LPHU6HOHFWLRQV
You can use the Read Status Entry option to view the current selection for the Presignal
function. To do so, press the keys in sequence:
&
&
]
V
&
The LCD display shows the current selections for System Functions, which includes the
three system timers. Figure 28 shows a sample LCD display of a System Function
screen with system timer selections:
)LJXUH  6DPSOH 6\VWHP )XQFWLRQ 6HOHFWLRQ 6FUHHQ
+RZ6
\
VWHP7LPHUV:RUN
The control panel can operate with special system timers: Silence Inhibit Timer, Auto
Silence Timer, and Alarm Verification Timer.
$XWR 6LOHQFH 7LPHU
A timer that functions like pressing the
ALARM
SILENCE
key. When the Auto Silence
Timer reaches its programmed value (300-600 seconds), the control panel automatically
shuts off all active outputs programmed as silenceable. To restart the Auto Silence
Timer, press the
ALARM
ACTIVATE
key.
$ODUP 9HULILFDWLRQ 7LPHU
A timer that directs the control panel to ignore a fire alarm for a smoke detector,
programmed for Alarm Verification, while the Alarm Verification Timer is counting.
Table 8 contains a summary of how the Alarm Verification Timer works.
7DEOH $ODUP 9HULILFDWLRQ 7LPHU 2
S
HUDWLRQ
6LOHQFH ,QKLELW 7LPHU
A timer that disables the
ALARM
SILENCE
key function for the programmed time
(0-300 seconds) when a fire alarm occurs. A Silence Inhibit Timer starts at the first fire
alarm and restarts with each new fire alarm.
6,/ ,1+  $872  9(5 ,)<  86$ 7,0(
7(50 1 $&
B
'/< < /RF7 %/,1.  67  $&6 1
6LOHQFH ,QKLELW 7LPHU VHW WR  VHFRQGV
$XWR 6LOHQFH 7LPHU VHW WR VHFRQGV
$ODUP 9HULILFDWLRQ 7LPHU VHW WR VHFRQGV
If The control panel does this
A second fire alarm occurs while the
Alarm Verification Timer is counting
Ignores the Alarm Verification Timer
The Alarm Verification Timer elapses
and a fire alarm still exists
Activates the fire alarm
The Alarm Verification Timer expires
and a fire alarm no longer exists
Increments the Alarm Verification counter (up to
99) for the device and returns to normal operation
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFC-600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFC-600 and is the answer not in the manual?

Notifier AFC-600 Specifications

General IconGeneral
BrandNotifier
ModelAFC-600
CategoryFire Alarms
LanguageEnglish

Related product manuals