Waterflow Circuit Operation
+RZ WR 2
HUDWH WKH &RQWURO 3DQHO
AFC-600 Operations PN 51033:A 3/8/99 35
:DWHUIORZ&LUFXLW2SHUDWLRQ
If a monitor module programmed with a
WATERFLOW
Type Code initiates a fire alarm,
the control panel disables the
ALARM
SILENCE
key and the Auto Silence Timer. Refer to
the AFC-600 Installation Manual for information on Waterflow circuits.
6W\OH2SHUDWLRQ
The control panel detects a trouble in an SLC wired and programmed for Style 6 or
Style 7 but continues to drive both ends of the line to maintain communication with
addressable devices on both segments of the SLC. The trouble latches and displays on
the panel as a Style 6 trouble type until you press reset the system. Style 7 configuration
of the SLC requires use of ISO-X modules.