Time, Date, and Holiday Functions
74 AFC-600 Operations PN 51033:A 3/8/99
Table 36 lists each Cross Zone option and the conditions required to activate the
Releasing Zone, according to the example shown in Figure 75.
7DEOH  ([DP
S
OH RI &URVV =RQH 6HOHFWLRQV
7LPH'DWHDQG+ROLGD\)XQFWLRQV
2YHUYLHZ
The control panel includes a real-time clock that displays the time-of-day, the date, and
the day-of-week. The clock includes a lithium battery backup. Time displays in a USA
format (12-hour time format with month/day/year) or a EUR (European) format as
shown in Figure 76.
)LJXUH  6DPSOH 86$ DQG (85 7LPH'DWH )RUPDWV
The control panel also provides Time Control zones F5 and F6 for time and date control
functions and zone F7 for holiday functions.
Cross Zone
Selection (Cross=)
Condition(s) Required to Activate the Releasing zone
Cross=
N
An alarm from any detector activates the releasing circuit.
Cross=
Y
An alarm from any two detectors activates the releasing circuit.
Cross=
Z
An alarm from two detectors mapped to different Software Zones, but
mapped to the same Releasing Zone.
• An alarm from D101 and D103 – detectors mapped to different
zones, but both list ZR1.
• An alarm from D102 and D104 – detectors mapped to different
zones, but both list ZR1 in their CBE.
Cross=
H
Activation of heat detector D104 and one smoke detector (D101,
D102, or D103).
7528%/ &21752/ 287387 &,5&8,7 0
= 23(1 &,5&8,7 30 021  0
86$ 7LPH DQG GDWH IRUPDW GHIDXOW
7528%/ &21752/ 287387 &,5&8,7 0
= 23(1 &,5&8,7  021  0
(85 7LPH DQG GDWH IRUPDW