Time, Date, and Holiday Functions
74 AFC-600 Operations PN 51033:A 3/8/99
Table 36 lists each Cross Zone option and the conditions required to activate the
Releasing Zone, according to the example shown in Figure 75.
7DEOH ([DP
OH RI &URVV =RQH 6HOHFWLRQV
7LPH'DWHDQG+ROLGD\)XQFWLRQV
2YHUYLHZ
The control panel includes a real-time clock that displays the time-of-day, the date, and
the day-of-week. The clock includes a lithium battery backup. Time displays in a USA
format (12-hour time format with month/day/year) or a EUR (European) format as
shown in Figure 76.
)LJXUH 6DPSOH 86$ DQG (85 7LPH'DWH )RUPDWV
The control panel also provides Time Control zones F5 and F6 for time and date control
functions and zone F7 for holiday functions.
Cross Zone
Selection (Cross=)
Condition(s) Required to Activate the Releasing zone
Cross=
N
An alarm from any detector activates the releasing circuit.
Cross=
Y
An alarm from any two detectors activates the releasing circuit.
Cross=
Z
An alarm from two detectors mapped to different Software Zones, but
mapped to the same Releasing Zone.
• An alarm from D101 and D103 – detectors mapped to different
zones, but both list ZR1.
• An alarm from D102 and D104 – detectors mapped to different
zones, but both list ZR1 in their CBE.
Cross=
H
Activation of heat detector D104 and one smoke detector (D101,
D102, or D103).
7528%/ &21752/ 287387 &,5&8,7 0